Settings (J4)
Alarm Channel Setting: Use this jumper to specify the
number of fan tachometer signals that will be monitored,
from 1 to 3. Each jumper setting label corresponds to
the number of fans to be monitored. For example, if only
two fan tachometer signals are going to be monitored set
the jumper to the 2 position. The factory setting is 3.
Settings (J5)
Trigger Speed (WA): Use this jumper to set the trigger
speed
Position L = 1000 PPM
Position M = 2000 PPM (Factory Setting)
Position H = 4000 PPM
Since fan tachometer circuits are designed with one,
two, or even more pulse outputs per revolution, settings
are listed in pulses per minute (PPM) rather than
revolutions per minute (RPM). Given the fans rated
speed (W) and number of pulses per revolution (N), use
the following formula to select the trigger speed (WA):
WA = W x N x 0.4
(Note: When used with a SmartFan speed controller the
factor in the above equation should be changed from 0.4
to 0.3.)
For example, a 3300-RPM fan with two pulses per
revolution would have a trigger speed (WA) of
WA = 3300 RPM x 2PPR x 0.4 = 2640 PPM
Since the 2000 PPM trigger is closest, set jumper J5 to
the M position.
The alarm trigger accuracy is +/- 20%.
LED Outputs (J6)
Both normally on (green) and normally off (red) LED
outputs are provided. Two leaded and three leaded
(common Cathode) Bi-colored LEDs can also be used.
Choose LEDs with rated forward voltage (Vf) between
1.6 and 2.4 VDC at forward current (If) of between 15
and 25 mA. Nominal current applied to the LEDs is 8
mA.
|
LED Connections
| Pin |
Function |
| K |
Cathode |
| R | Active HI for red LED connection |
| G | Activee LOW for green LED |
| K | Cathode |
Isolated Alarm Outputs (J8)
These outputs provide both normally open and normally
closed isolated outputs permitting connection to logic
circuits or other loads with no electrical connection to the
TachScan-3 circuit.
Part Numbers 030M320-F and 030M3205-F provide
simultaneous open collector outputs from optical
isolators, which are intended to drive logic circuits.
These outputs can sink up to 1.0 mA at 0.4 VDC. A
maximum of 30 VDC can be applied to alarm terminals.
The normally closed output also triggers in the event of
cooling system power failure.
Part Numbers 030M320R-F and 030M320R4-F provide
simultaneous outputs from a Dual-Pole MOS Relay,
which are intended to drive heavy loads. These outputs
have a maximum on-state resistance of 50 O. Maximum
sinking current is 100 mA. A maximum of 230 VAC can
be applied to alarm terminals. The normally open output
also triggers in the event of cooling system power failure.
Isolated Output Connections
| Part No. |
Pin 1A |
Pin 1B |
Pin 2A |
Pin 2B |
030M320-F &
030M3205-F |
NC Emitter |
NC Collector |
NO Emitter |
NO Collector |
030M320R-F &
030M320R4-F |
NC |
NC |
NO |
NO |
Note: At power-up, all outputs are held in the normal state
for 10 seconds permitting the fans to come up to speed.
|