  • Testing, Troubleshooting & Technical Data


  • Testing & Technical Data

    Motor Compatibility

    For maximum motor life without using a line filter, the use of an inverter duty motor is recommended.


    Changing Control Settings

    The Stratus will not recognize any changes in switch settings made with power applied. To avoid electrical shock, it is recommended that power be turned off for 30 seconds before changing any switch settings.


    Electrical Noise Emissions and Filtering

    Electrical noise emissions (EMI) are highly dependent on load and environment. For many applications no additional filtering is required to meet EN55011/FCC class A emissions standards. For applications requiring additional filtering CRI recommends the following filters or equivalents:

    EN55011/FCC class A:
    150kHz - 30mHz
    EN55011/FCC class B:
    10kHz - 30mHz
    Filter Concepts: LE series
    www.filterconcepts.com
    Filter Concepts: LX series
    www.filterconcepts.com
    Corcom S series
    www.corcom.com
    Corcom Q series
    www.corcom.com


    Controlling Multiple Motors

    Multiple motors wired in parallel can be controlled from one Stratus VFD as long as maximum peak (startup) currents do not exceed 10 Amps.


    Control Accuracy and Hysteresis

    Control signal accuracy is as follows:
    • Voltage: +/- 0.38VDC
    • Current: +/- 0.4mA
    • Temperature: +/- 1.5°C
    In alarm conditions, loss of signal and ON/OFF feature, hysteresis is added to eliminate cycling. Hysteresis is as follows:
    • Voltage: +/- 2%
    • Current: +/- 1.5%
    • Temperature: 1-2°C

    RoHS compliance

    Contact customer service for the latest compliance information.


    Maximum Fan Currents

    Some motors draw higher current at less than maximum voltage. Contact motor manufacturer for details.


    HiPot Testing

    The Stratus is designed to withstand HiPot testing to 1500Vrms, line input to analog input, motor output to analog input.


    Current Derating

    TheStratus may be run above 40˚C.  However, the maximum current ratings will decline according the chart below.


    SmartFan Nimbus Current Derating vs. Ambient Temp.

    Figure 6


    Specifications:
    • Power Source: 95 - 250 VAC
    • Frequency: 47 - 64 Hz
    • Output Power at 40°C:
      • 1 kW load rated for three-phase
      • 800 Watts load rated for single-phase @ 240VAC
      • 400 Watts load rated for single-phase @ 120VAC
    • Maximum peak (startup) current: 10 Amps
    • Storage Temperature: -40°C to 125°C
    • Operating Temperature: -25° to 70°C
    • Thermal shutdown at 100°C
    • Relative Humidity: 95% non-condensing
    • Weight (no cover): 1.31 lb (594 grams)
    • Weight (with cover): 1.98 lb (898 grams)