USING REMOTE POWERED TRANSDUCER MODE
When used in the remote transducer mode, the
Nimbus-HP can power and control from most 0-5VDC
transducers (humidity, pressure, flow etc.) with a
maximum supply current of 5mA. To set the Nimbus to
remote transducer mode, see table 2.
Setting Control Parameters (switch #3, 4, 5, 6)
To customize the control slope to your transducer, use
DIP switches 3 & 4 to set idle or minimum speed
voltage, use switches 5 & 6 to set full speed control
voltage. See table 6 and figure 4 for details.
 |
Fan On / Fan Off Feature (switch #1)
To turn fans off automatically when transducer voltage
drops below VDC (min), set switch #1 to the ON
position. To keep fans running at idle speed below the
VDC (min), set switch #1 to the OFF position. See
figure 4.
Setting Idle Speed (switch #2)
The idle speed is the minimum voltage (as a % of supply
voltage) supplied to the fan. When used in the remote
transducer mode, the Nimbus-HP can be set for idle
speeds of 30% by setting DIP switch #2 to OFF or 60%
by setting DIP switch #2 to ON. Other idle speeds can
be supplied, contact customer service for details. See
figure 4.
|