  • SMARTFAN FUSION DC FAN SPEED CONTROL AND ALARM STANDARD CONFIGURATION

    The Fusion-9 is intended to be configured via an I2C bus. If no I2C bus is connected the Fusion-9 will default to temperature based speed control as follows.

    • Temperature is monitored by the remote sensor
    • Control (full speed) temperature is 40ºC
    • Temperature slope is 5ºC
    • Idle speed (temperature below 35ºC) is ~13 VDC
    • Fan alarm is set at 2000 PPM with 9 fans
    • LED and MOS alarms are active for fan alarms and external sensor failure (open).
    If your system does not utilize an I2C bus and the temperature control parameters above do not meet your needs, the Fusion can be configured at the factory for special temperature control parameters. Contact Control Resources’ application engineering for assistance.

    SMARTFAN FUSION DC FAN SPEED CONTROL AND ALARM SPECIALIZED CONFIGURATIONS

    The following parameters can be specialized through software modification:
    • Relationship between sensed temperature and fan voltage
    • Additional temperature sensor inputs
    • Analog control input (voltage / PWM control)
    • Fan speed control based on differential temperature
    • Fan speed alarm trigger point
    • I2C bus status register

    SMARTFAN FUSION DC FAN SPEED CONTROL AND ALARM CUSTOMIZED CONFIGURATION

    Contact Control Resources’ application engineering with special or custom requirements.

    ADDITIONAL MANUAL PAGES

    Use the links below for addtional manual pages or for a complete manual or click on the Operation/Installation Manual PDF link above.





    Control Resources Home | News and Info | Technical Data | Catalog | Contact Us | Applications | About Control Resources | Site Map
    Control Resources Incorporated 11 Beaver Brook Road Littleton MA, 01460 USA Tel: 978-486-4160 Fax: 978-486-4772 email: sales@controlres.com