|
Thermistor Choose an air, surface or liquid temperature sensor from
the CRI catalog.
Connect to J4, IN and GND (polarity neutral).
Voltage or Current signal control Connect 0 -10VDC or 0 -20mA control signal + to J4, IN
and – to J4, GND. CAUTION: Reversing + and - may
damage the control.
Remote Transducer The Cirrus can control fan speed based on a remote
transducer. For transducers that require 18VDC or less
to power, the Cirrus can power the transducer as well.
To connect and power a transducer, attach the supply
voltage lead to J4,OUT attach the output voltage lead to
J4, IN, attach ground lead to GND. To adjust a supply
voltage for the transducer, see step A) Transducer or
Alarm Power.
Alarm Conditions and Connections For the off-the-shelf Cirrus, an alarm signal will be
triggered if any of the conditions in table 5 are met. The
Cirrus can also be preprogrammed at the factory to
provide any number of custom alarm conditions and
configurations.

The alarm output is a normally open (NO), open collector
referenced to isolated ground. When no alarm condition
is present, the relay is closed and can conduct up to 100
ma DC, of load current. When the alarm is triggered, the
transistor opens, and can support up to 100 VDC across
its terminals. See figures 9a, 9b, 9c or 9d for possible
alarm configurations.


|